Setting up the modules to transfer data using either the Global Data modules (140 NOE 771 01, 140 NOE 771 11, or 140 CPU 651 x0 mobules) or the I/O scanner utility (in the 140 NOE 771 00/01/11 modules and the 140 CPU 651 50/60 modules) using an embedded Web server to access diagnos tics and online configurations for the module. Z140 NOE 771 01 z140 NOE 771 10 z140 NOE 771 11 This manual provides you with the knowledge to begin using a Quantum PLC to communicate with devices over an Ethernet network. Acer aspire revo r3610 manual download. This manual includes information about: zhardware architecture of a Quantum Ethernet TCP/IP module designed to fit into a single slot on the standard Quantum backplane.
140 Noe 771 11 Manual
- With a Domino 'A Series' printer using the A-comm Communications Protocol. The QUCM-OE must be used in the local Quantum PLC processor rack. The module is configured as an NOE-771-01 in the PLC and the I/O Scanner table is used to de-fine the location of.
- Apr 05, 2017 Keep in mind this feature cannot generate an IP address for the actual 140 NOE module but rather for connecting I/O modules to that NOE module once it is installed. Just use the module’s HTTP web page to add, edit, and remove devices from the BootP server database. 140 NOE 771 01, 140 NOE 771 11 and 140 NOE 771 21 IP Addresses.
Abc
Hi
I'm trying to setup communications between plc and a network switch (the switch is on a particular noetwork at our site)
I'm using a NOE 771 11 (modicon quantum card) and the CPU is a 130 CPU 113 03S. There are a few input and out put cards on the same rack.
the connection from the network to NOE is made using a combination of fibre/media converter and cat6, the distance between the too is about 500mts approx, the issue i m having is on the NOE it shows a fault and the Run flashes 3 times which on the manual says no link or damaged cable in the connection, i have unplugged the cat6 from the now and hooked it into a laptop, i have tried pinging other Noes on the network for other PLC's and im able to do so, i have also gone the other way round and pinged this laptop from another machine, this tells me that the connection is good however the NOE run flashes 3 times hence status there is a problem with the link
We use concept program and i have changed the config extensions under Ethernet I/Oscanner
Internet address
10.218.64.146
gateway 10.218.64.254
subnet 255.255.255.128
Frame type Ethernet 2
Master module slot Slot 7 140 NOE 771-01
the subnet and gateway is same to that of the network, the fact that when i have a laptop connected on that end tells me that there is no issues with IP and gateway etc
i have tried changing the NOE card out and there's been no change
I think there is some other setting which i'm unaware of what to change
this plc is not linked or not talking to any other plc so no need for any comms blocks in concept
Done a full download on the plc
i might try changing out the CPU to a newer one but any other ideas that you guys may have would me much appreciated, Thanks
I'm trying to setup communications between plc and a network switch (the switch is on a particular noetwork at our site)
I'm using a NOE 771 11 (modicon quantum card) and the CPU is a 130 CPU 113 03S. There are a few input and out put cards on the same rack.
the connection from the network to NOE is made using a combination of fibre/media converter and cat6, the distance between the too is about 500mts approx, the issue i m having is on the NOE it shows a fault and the Run flashes 3 times which on the manual says no link or damaged cable in the connection, i have unplugged the cat6 from the now and hooked it into a laptop, i have tried pinging other Noes on the network for other PLC's and im able to do so, i have also gone the other way round and pinged this laptop from another machine, this tells me that the connection is good however the NOE run flashes 3 times hence status there is a problem with the link
We use concept program and i have changed the config extensions under Ethernet I/Oscanner
Internet address
10.218.64.146
gateway 10.218.64.254
subnet 255.255.255.128
Frame type Ethernet 2
Master module slot Slot 7 140 NOE 771-01
the subnet and gateway is same to that of the network, the fact that when i have a laptop connected on that end tells me that there is no issues with IP and gateway etc
i have tried changing the NOE card out and there's been no change
I think there is some other setting which i'm unaware of what to change
this plc is not linked or not talking to any other plc so no need for any comms blocks in concept
Done a full download on the plc
i might try changing out the CPU to a newer one but any other ideas that you guys may have would me much appreciated, Thanks